PURPOSE
ENERGET 1 uninterruptible power supply system is designed to provide stabilized voltage of three-phase AC network at 380V and ensure backup power supply in case of main power line failure.
FIELDS OF APPLICATION
- objects classified as first category of power supply reliability
- objects requiring autonomous power supply, including those located in regions with unfavorable climatic conditions
VERSION
- the system is enclosed in a thermally insulated metal container which houses a diesel generator, an uninterruptible power supply source, and a controller
- the container is equipped with a self-safety system, access control and management system, security and fire alarm system, automatic fire extinguishing system, heating and ventilation systems, and protective grounding
FEATURES
- automatic switching to backup power supply from the diesel generator in case of main line failure
- maintenance of equipment power supply from the uninterruptible power supply source during the period between main line failure and full launch of the diesel generator
- power supply from the backup source for any type of energy consumer
- providing self- security of the system
- access control to the container by digital code or proximity card
- early detection of smoke, air temperature increase, or fire inside the container
- automatic activation of the fire extinguishing system if necessary
- maintenance of working air temperature inside the container
PECULIARITIES
- seamless switching to the power generation mode from the diesel generator
- automatic startup of the diesel generator immediately after seamless switching
- inverter that provides a clean sinusoidal waveform of the output voltage identical to the centralized power supply network
- inverter’s high efficiency in combination with a set of battery packs ensures lasting operation time and reduces recharge time
- remote monitoring of the system status via Ethernet
- self-security system
- extended temperature range that allows the system to be used in complex climatic conditions
- fuel tank located inside the container preventing unauthorized fuel usage
SCOPE OF SUPPLY
Name |
Quantity |
Thermos container STVF.301179.002 |
1 pc. |
Power cabinet STVF.426431.004 |
1 pc. |
Insulated rack STVF.426479.048 |
1 pc. |
Switchgear cabinet STVF.426479.053 |
1 pc. |
Video camera SVK-855 STVF.426459.053 |
5 pcs. |
Code panel STS-708 STVF.431295.035 |
1 pc. |
Controller STS-423 STVF.426469.089 |
1 pc. |
Diesel generator STVF.561343.001 |
1 pc. |
Inverter MAP 15 kW (48V) |
3 pc. |
Optex LX-402 sensor |
4 pcs. |
IO-102-20 A2M detector |
3 pcs. |
Smoke-optical point fire detector IP 212-141 |
2 pcs. |
IP 535-27 "IPR-Ex" manual fire detector |
1 pc. |
PC-186 power cable 1.8 m |
1 pc. |
Reversible 220V actuator KVU |
2 pcs. |
Buran-2.5-2C powder fire extinguishing module |
1 pc. |
Warning light "POWDER! DO NOT ENTER" |
1 pc. |
Convection heater CH 2000-2001 |
1 pc. |
Sound warning device (two-tone siren) Ademco 702 |
1 pc. |
Security-fire warning device Astra-10 |
1 pc. |
LED emergency light LEDx30 |
2 pcs. |
Industrial LED luminaire |
2 pcs. |
GX 12-200 DELTA rechargeable battery |
10 pcs. |
Spare parts set-O STVF.425973.109 |
1 set |
Mounting parts set STVF.425951.042 |
1 set |
Protective parts set STVF.425959.019 |
1 set |
Operating documents list* STVF.565312.001 VE |
1 copy |
Operating guidelines** STVF.565312.001 RE |
1 copy |
Formulary STVF.565312.001FO |
1 copy |
* Full contents of the operational design documentation is in accordance with the list of operational documents ** The operating guidelines are supplied in a single copy when shipped with a batch of products or as part of a system. For single deliveries, the operating guidelines are supplied for each unit. Operating guidelines are available at: http://stilsoft.ru |
DESCRIPTION OF SYSTEM PARTS
- thermos container is designed to accommodate the system's components and equipped with hermetically closing slide doors
- diesel generator provides power to consumers with a variable three-phase current of 400 V and a frequency of 50 Hz
- inverter with a set of battery packs provides uninterrupted and/or autonomous power supply to equipment operating at 220/230 V (or 380/400 V for a three-phase system)
- STS-423 controller provides climate control inside the container, access control, fire protection, security, and storage of video archives
- STS-708 code panel provides authorized access to the container by code or proximity card
- SVK-855 cameras in a vandal-resistant case support the "day/night" mode, equipped with mechanical IR filters and built-in IR illumination, and serve to ensure the system's self-security
- Optex LX-402 detector is designed to protect the system from unauthorized intrusion by detecting potential intruders approaching the container
- BURAN-2.5-2S powder fire extinguishing module provides localization and extinguishing of fire in the container
RELIABILITY AND WARRANTY
- System warranty period - 10 years
- Battery pack warranty period - 2 years
- Designated system operation period is 10 years
Parameter name |
Value |
Main generator power, kW/kVA (minimum) |
30/37.5 |
Backup generator power, kW/kVA (minimum) |
33/41.2 |
Frequency, Hz |
50 |
Input/output voltage, V |
400 |
Current type |
AC three-phase |
Autonomous operation time at 100% power, h (minimum) |
48 |
Resource before major repair, h (minimum) |
25000 |
Fuel type |
Diesel |
Fuel consumption, l/h - at 75% load - at 100% load |
6.9 8.3 |
Total fuel tank capacity, l (minimum) |
450 |
Generator startup time, min (maximum) |
10 |
"Grid-Battery" transition time, ms (minimum) |
20 |
"Battery-Grid" transition time, ms (minimum) |
2 |
System operating time on fully charged batteries at maximum load of 30 kW, min (minimum) |
20 |
Total capacity of rechargeable batteries, Ah |
1600 |
Rated DC voltage on battery bus, V |
48, 12 |
Number of batteries, pcs |
8 |
Number of batteries to start diesel generator, pcs |
2 |
Rated voltage of batteries for diesel generator, V |
12 |
Battery type |
Gel |
Power supply delivery time |
Linear-interactive |
Lubrication system volume, l |
12 |
Oil consumption at 100% load, l/h |
0.02 |
Oil type |
M-5Z/10G1 |
Short-circuit protection |
Yes |
Overload protection |
Yes |
Overheat protection |
Yes |
Interference filtration |
Yes (partial) |
Protection against high voltage pulses |
Yes |
Automatic fire suppression system |
Yes |
Video surveillance system |
Yes |
Manual control system |
Yes |
Security system |
Yes |
Access control system |
Yes |
Average service life, not less than, years |
10 |
Range of operating temperatures, °C |
from -60 to +60 |
Dimensions, mm |
3500x2200x 2300 |
Weight with empty fuel tank and without batteries, kg (maximum) |
3000 |